Customization: | Available |
---|---|
Interface/Bushing: | Type C (EN50181) |
Rated Voltage: | 10kV, 20kV |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Kit reference | Suit for diameter over XLPE insulation | Conductor size (17.5kV) | Conductor size (24kV) |
CJB20-630-1#, CJBK20-630-1# | 16.5-23 mm | 35-95 sq.mm | 25-70 sq.mm |
CJB20-630-2#, CJBK20-630-2# | 23-28 mm | 120-185 sq.mm | 95-150 sq.mm |
CJB20-630-3#, CJBK20-630-3# | 28-36 mm | 240-400 sq.mm | 185-300 sq.mm |
CJB20-630-4#, CJBK20-630-4# | 36-40 mm | 500 sq.mm | 400-500 sq.mm |
CJB20-630-5#, CJBK20-630-5# | 40-45 mm | 630 sq.mm | 630 sq.mm |
Test Item | Test value |
AC voltage withstand | 54kV, 5min |
AC voltage withstand | 30kV, 15min |
Partial discharge | 20kV, ≤10pC |
Heating cycles voltage test | 30 cycles in air, 30 cycles under water at 95-100°C, 30kV |
Thundering impulse voltage withstand | 125kV at 10 positive and 10 negative |
Screen resistance | Not exceed 5000Ω |
Screen leakage current | Maximum 0.5mA at 24kV |
Thermal short-circuit test | No visible deterioration at 37.3kA, 2s |
Dynamic short-circuit test | No visible deterioration at 131.9kA, 10ms |