Customization: | Available |
---|---|
Interface: | Type A (EN50181) |
Rated Voltage: | 10kV, 20kV |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product type and size | for diameter over XLPE insulation Ø (mm) | Suitable cable size (sq.mm) | |||
Um=12kV cable | Um=17.5kV cable | Um=24kV cable | Um=36kV cable | ||
Size 1 | Ø17~Ø22 | 70~120 | 35~70 | 25~50 | |
Size 2 | Ø22~Ø26 | 150~185 | 95~150 | 70~120 | 25~50 |
Size 3 | Ø26~Ø29 | 240 | 185~240 | 150~185 | 70~95 |
Test Item | Test value |
AC voltage withstand | 54kV, 5min |
AC voltage withstand | 30kV, 15min |
Partial discharge | 20kV, ≤10pC |
Heating cycles voltage test | 30 cycles in air, 30 cycles under water at 95-100°C, 30kV |
Thundering impulse voltage withstand | 125kV at 10 positive and 10 negative |
Disconnect / connect | Five complete operations, no visible damage to contact |
Screen resistance | Not exceed 5000Ω |
Thermal short-circuit test | No visible deterioration at 12.2kA, 2s |
Dynamic short-circuit test | No visible deterioration at 44.3kA, 60ms |