Customization: | Available |
---|---|
Interface/Bushing: | Type C (EN50181) |
Rated Voltage: | 10kV, 20kV |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Kit reference (No.) |
Suit for diameter over XLPE insulation (mm) |
Conductor size in mm2 (for guidance only) | |
17.5kV (Um) | 24kV (Um) | ||
CJ20-630D-1#, CJK20-630D-1# | 16.5-23 | 35, 50, 70, 95 | 25, 35, 50, 70 |
CJ20-630D-2#, CJK20-630D-2# | 23-28 | 120, 150, 185 | 95, 120, 150 |
CJ20-630D-3#, CJK20-630D-3# | 28-36 | 240, 300, 400 | 185, 240, 300 |
CJ20-630D-4#, CJK20-630D-4# | 36-40 | 500 | 400, 500 |
CJ20-630D-5#, CJK20-630D-5# | 40-45 | 630 | 630 |
Test Item | Test value |
AC voltage withstand | 54kV, 5min |
Partial discharge | 20kV, ≤10pC |
Thundering impulse voltage withstand | 125kV at 10 positive and 10 negative |