Customization: | Available |
---|---|
Interface: | Type C (EN50181) |
Rated Voltage: | 10kV, 20kV, 30kV |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Kit reference | Suit for diameter over XLPE insulation | Conductor size (36kV) |
CJB30-630-1#, CJBK30-630-1# | 23-28 mm | 35-70 sq.mm |
CJB30-630-2#, CJBK30-630-2# | 28-36 mm | 95-185 sq.mm |
CJB30-630-3#, CJBK30-630-3# | 36-40 mm | 240-300 sq.mm |
CJB30-630-4#, CJBK30-630-4# | 40-45 mm | 400-500 sq.mm |
CJB30-630-5#, CJBK30-630-5# | 44-49 mm | 630 sq.mm |
Test Item | Test value |
AC voltage withstand | 81kV, 5min |
AC voltage withstand | 45kV, 15min |
Partial discharge | 30kV, ≤10pC |
Heating cycles voltage test | 30 cycles in air, 30 cycles under water at 95-100°C, 45kV |
Thundering impulse voltage withstand | 170kV at 10 positive and 10 negative |
Screen resistance | Not exceed 5000Ω |
Screen leakage current | Maximum 0.5mA at 36kV |
Thermal short-circuit test | No visible deterioration at 31kA, 2s |
Dynamic short-circuit test | No visible deterioration at 112kA, 10ms |