Test item | IEC60840:2004 | Test result |
Partial discharge | 96kV, <5pC | 128kV, <1pC |
Heating cycles voltage test | 128kV, 95-100ºC, 8h heating, 16h cooling, 20 cycles | Pass |
Partial discharge | 96kV, <5pC | 128kV, <1pC, no change after heating cycles |
Impulse voltage test | 10 positive and 10 negative impulses at 550kV | No breakdown or flashover at 650kV |
A.C. voltage withstand | 160kV, no breakdown or flashover for 15min | 160kV, no breakdown or flashover |
Sealing test | No leakage at 0.2MPa for 1hr | No leakage at 0.2MPa for 1hr |
Thermal short-circuit test |
40kA, 3s, no spoilage, distortion or weld | |
Dynamic short-circuit test |
100kA, 0.1s, no spoilage, distortion or weld | |
Pressure explosion test | 1.5MPa, no distortion or leakage | |
A.C. voltage withstand (additional test) |
192kV, 15min no breakdown or flashover | |
Each piece will be tested Partial discharge 96kV; A.C. voltage withstand 160kV, 30min before leaving factory. |