Test Item | Test value |
AC voltage withstand | 54kV, 5min |
AC voltage withstand | 65kV, 1min |
Partial discharge | 20kV, ≤5pC |
Thundering impulse voltage withstand at 10 positive and 10 negative | 125kV |
Thermal short-circuit | 31.5kA, 4s |